DC VOLTAGE |
48
|
RATED CURRENT |
210
|
CURRENT RANGE |
0 ~210A
|
RATED POWER |
10080
|
RIPPLE & NOISE |
200mVp-p
|
VOLTAGE ADJ.RANGE |
Can be adjusted via built-in potentiometer 47 ~ 57.6V
|
VOLTAGE TOLERANCE |
±1.0%
|
LINE REGULATION |
±0.5%
|
LOAD REGULATION |
±0.5%
|
SET UP, RISE TIME |
2200ms, 80ms at full load
|
HOLD UP TIME |
20ms / 230VAC at 75% load 14ms / 230VAC at full load
|
INPUT VOLTAGE RANGE |
3ψ3-wire /△196 ~ 305VAC or 3ψ4-wire / Y 340 ~ 530VAC
|
FREQUENCY RANGE |
47 ~ 63Hz
|
POWER FACTOR |
0.95/230VAC(400VAC) at full load
|
EFFICIENCY |
91%
|
AC CURRENT |
30A/230VAC(3ψ3-wire /△) 18A/400VAC(3ψ4-wire / Y)
|
INRUSH CURRENT |
150A/230VAC(3ψ3-wire /△) 100A/400VAC(3ψ4-wire / Y)
|
LEAKAGE CURRENT |
<7mA /△305VAC(Y 530VAC)
|
OVERLOAD |
100 ~ 112% rated output power User selectable continuous constant current limiting or constant current limiting with delay shutdown after 5 seconds, re-power on to recover
|
OVER VOLTAGE |
Protection type : Shut down o/p voltage, re-power on to recover 60 ~ 67.2V
|
OVER TEMPERATURE |
Shut down o/p voltage, recovers automatically after temperature goes down
|
OUTPUT VOLTAGE PROGRAMMABLE |
Adjustment of output voltage is allowable to between 20 ~ 120% of nominal output voltage. Please refer to the Function Manual.
|
OUTPUT CURRENT PROGRAMMABLE |
Adjustment of output current is allowable to between 20 ~ 100% of rated current. Please refer to the Function Manual.
|
CURRENT SHARING |
Up to 20000W or (1+1) units. Please refer to the Function Manual.
|
AUXILIARY POWER |
12V@0.1A(Only for Remote ON-OFF control)
|
REMOTE ON-OFF CONTROL |
By electrical signal or dry contact Power ON:open Power OFF:short. Please refer to the Function Manual.
|
REMOTE SENSE |
Compensate voltage drop on the load wiring up to 0.3V. Please refer to the Function Manual.
|
ALARM SIGNAL OUTPUT |
AC fail, DC OK, fan fail, OTP. Please refer to the Function Manual.
|
WORKING TEMP |
-30 ~ +70℃(Refer to "Derating Curve")
|
WORKING HUMIDITY |
20 ~ 90% RH non-condensing
|
STORAGE TEMP HUMIDITY |
-40 ~ +85℃, 10 ~ 95% RH
|
TEMP. COEFFICIENT |
±0.03%/℃(0 ~ 50℃)
|
VIBRATION |
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
|
SAFETY STANDARDS |
UL60950-1, TUV EN60950-1 approved
|
WITH STAND VOLTAGE |
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
|
ISOLATION RESISTANCE |
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
|
EMC EMISSION |
Refer to attachment
|
EMC IMMUNITY |
Refer to attachment
|
MTBF |
50K hrs min. Telcordia SR-332 (Bellcore) ; 17K hrs min. MIL-HDBK-217F (25℃)7F (25℃)
|
DIMENSION |
540*424*83.5mm (L*W*H)
|
PACKING |
23.5Kg; 1pcs/23.5Kg/2.5CUFT
|